PLX51-PBS

PLX51-PBS PROFIBUS DP Slave to EtherNet/IP™ Gateway

PLX51-PBS

The PLX51-PBS gateway provides connectivity to EtherNet/IP™ networks for PROFIBUS DP networks by operating as a PROFIBUS DP slave.

For easy integration to a Rockwell Automation Controller, the gateway and configuration software create dynamic AOI’s based on the user configuration to add logical tag names to the PLC project file. Thus, reducing the overall programming time.

With advanced tools such as a built in PROFIBUS DP packet capture utility, PROFIBUS DP network commissioning time can be greatly reduced. 

Dual Ethernet ports of the module can support either DLR (Device Level Ring) topology, or can be used as an embedded switch for flexible installation options. 

Интеграция платформы

Click on image(s) to enlarge
Drag with the mouse. Click for close.

Особенности и преимущества

  • Supports DLR for EtherNet/IP networks
  • PROFIBUS slave OR multi-slave support
  • PROFIBUS packet capture tool built in

Configuration

The PLX50 Configuration Utility software is used for configuration and troubleshooting of the module.  The stand-alone configuration utility allows users to define the setup and configuration of the PROFIBUS DP module, connections with Rockwell Automation controllers and devices over EtherNet/IP, and build custom Add-On Instructions (AOIs) to be imported into Studio 5000 applications. 

With the ability to import custom AOI’s into the Studio 5000 environment and advanced PROFIBUS DP tools such as the packet capture utility, commissioning time of a network can be greatly reduced.  

Характеристики

General Specifications – PROFIBUS DP Slave

The PROFIBUS DP-V0 Slave driver provides a powerful and easy-to-use interface between a PROFIBUS DP network and other networks.

This slave implementation emulates up to 10 individual nodes on a PROFIBUS DP network. It allows access to up to 1536 bytes of cyclic PROFIBUS Input data and up to 1536 bytes of cyclic PROFIBUS Output data.

For installations that require more than the 244 byte max cyclic PROFIBUS DP data exchange, this module allows users to emulate up to 10 nodes, eliminating the need for complex DPV1 Read/Write messages to a PROFIBUS DP node while improving data throughput.  

EtherNet/IP™ Server

As an EtherNet/IP server, the gateway can support up to 4 Class 1 I/O connections back to a Controller on an EtherNet/IP network. Additionally, the server can respond to Class 3 messages from an EtherNet/IP client for the transfer of Status and PROFIBUS DP data.

 

EtherNet/IP

 

Connector

RJ45

Conductors

CAT5 STP/UTP

ARP Connections

Max 40

TCP Connections

Max 40

CIP Connections

Max 10

Communication Rate

10/100Mbps

Duplex Mode

Full / Half / Auto Negotiate

Auto MDIX

Yes

PROFIBUS DP

 

Protocol

PROFIBUS DP Slave

Baud Rate

9600, 19.200, 45.5 kbps, 93.75 kbps, 187.5 kbps, 500 kbps, 1.5 Mbps, 3 Mbps, 6 Mbps, 12 Mbps

Support

DPV0 or DPV1

Cyclic I/O data

Input: 1536 bytes
Output: 1536 bytes

Stop bits

1

Характеристики оборудования

Specification

Description

Emissions

IEC 61000-6-4

ESD Immunity

EN 61000-4-2

Radiated RF Immunity

IEC 61000-4-3

EFT/B Immunity

IEC 61000-4-4

Surge Immunity

IEC 61000-4-5

Conducted RF Immunity

IEC 61000-4-6

Physical

Specification

Description

Enclosure Rating

IP20, NEMA/UL Open Type

Temperature

-20 to 70 °C

Earth Connection

Yes, terminal based

Dimensions (H x W x D)

5.86 x 1.33 x 4.56 in
149 x 34 x 116 mm

Power Requirements

Input: 10 to 36V DC

Power Consumption

85mA @ 24V => 2.04W

Power Connector

3-way terminal

Conductors

24 to 18 AWG

одобрения и сертификаты

Ex Certificate (ATEX Directive) 278,54 kB Последнее изменение 04.09.19
CB Safety 1,97 MB Последнее изменение 04.09.19
UL/cUL; Class1, Div 2 235,70 kB Последнее изменение 04.09.19
ODVA EtherNet/IP Declaration of Conformity 37,88 kB Последнее изменение 04.09.19